Technical specifications

Number of poles4
Rated permanent current Iu1000A
Degree of protection (IP)IP30
Position of connection for main current circuitBack side
Rated voltage690 - 690V
Motor drive integratedNo
Overload release current setting400.0 - 1000A
Number of auxiliary contacts as change-over contact4
With switched-off indicatorYes
Type of control elementPush button
Type of electrical connection of main circuitBolt connection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release1500.0 - 15000A
Adjustment range short-term delayed short-circuit release1000 - 10000A
Integrated earth fault protectionYes
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device fixed built-in technique
With under voltage releaseNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA059223R1 | E1N 1000 PR121/P-LSIG IN=1000A 4P F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles

4

Rated permanent current Iu

1000A

Degree of protection (IP)

IP30

Position of connection for main current circuit

Back side

Rated voltage

690 .. 690V

Motor drive integrated

Overload release current setting

400.0 .. 1000A

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

Type of control element

Push button

Type of electrical connection of main circuit

Bolt connection

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Suitable for DIN rail (top hat rail) mounting

Adjustment range undelayed short-circuit release

1500.0 .. 15000A

Adjustment range short-term delayed short-circuit release

1000 .. 10000A

Integrated earth fault protection

Motor drive optional

DIN rail (top hat rail) mounting optional

Device construction

Built-in device fixed built-in technique

With under voltage release

Complete device with protection unit