Aleta.hr
Main Product Image

1SDA059268R1 | E2N 1000 PR121/P-LSIG IN=1000A 4P W MP

Code: 1594315

ManufacturerRAZNO
Catalog number1SDA059268R1
Type
EAN code8015644616298

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Integrated earth fault protection

Yes

Suitable for DIN rail (top hat rail) mounting

No

Number of auxiliary contacts as normally closed contact

0

Device construction

Built-in device slide-in technique (withdrawable)

DIN rail (top hat rail) mounting optional

No

Adjustment range short-term delayed short-circuit release

1000 - 10000A

Adjustment range undelayed short-circuit release

1500.0 - 15000A

Type of electrical connection of main circuit

Connection at separate chassis part

Rated permanent current Iu

1000A

Complete device with protection unit

Yes

With switched-off indicator

Yes

Number of poles

4

Position of connection for main current circuit

Connection at separate chassis part

Overload release current setting

400.0 - 1000A

Number of auxiliary contacts as normally open contact

0

Degree of protection (IP)

IP30

Rated voltage

690 - 690V

Type of control element

Push button

Motor drive optional

Yes

Number of auxiliary contacts as change-over contact

4

Motor drive integrated

No

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA059268R1 | E2N 1000 PR121/P-LSIG IN=1000A 4P W MP

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as normally closed contact

0

Device construction

Built-in device slide-in technique (withdrawable)

DIN rail (top hat rail) mounting optional

Adjustment range short-term delayed short-circuit release

1000 .. 10000A

Adjustment range undelayed short-circuit release

1500.0 .. 15000A

Type of electrical connection of main circuit

Connection at separate chassis part

Rated permanent current Iu

1000A

Complete device with protection unit

With switched-off indicator

Number of poles

4

Position of connection for main current circuit

Connection at separate chassis part

Overload release current setting

400.0 .. 1000A

Number of auxiliary contacts as normally open contact

0

Degree of protection (IP)

IP30

Rated voltage

690 .. 690V

Type of control element

Push button

Motor drive optional

Number of auxiliary contacts as change-over contact

4

Motor drive integrated

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA