Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1000A
Overload release current setting
400.0 - 1000A
Adjustment range short-term delayed short-circuit release
600.0 - 600.0A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Integrated earth fault protection
Yes
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Rated voltage
690 - 690V
With switched-off indicator
Yes
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
No
Motor drive optional
Yes
Type of control element
Push button
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Motor drive integrated
No
Complete device with protection unit
Yes
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
Number of poles
4
From same serie
1SDA059324R1 | E2S 1000 PR122/P-LSIG IN=1000A 4P W MP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1000A
Overload release current setting
400.0 .. 1000A
Adjustment range short-term delayed short-circuit release
600.0 .. 600.0A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Integrated earth fault protection
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Rated voltage
690 .. 690V
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Motor drive optional
Type of control element
Push button
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Motor drive integrated
Complete device with protection unit
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Number of poles
4