Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Rated permanent current Iu
1000A
Adjustment range short-term delayed short-circuit release
1000 - 10000A
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
690 - 690V
Integrated earth fault protection
Yes
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
No
Overload release current setting
400.0 - 1000A
Complete device with protection unit
Yes
Position of connection for main current circuit
Back side
Motor drive integrated
No
Number of auxiliary contacts as change-over contact
4
Number of poles
3
Type of control element
Push button
Motor drive optional
Yes
Degree of protection (IP)
IP30
With switched-off indicator
Yes
Device construction
Built-in device fixed built-in technique
From same serie
1SDA059353R1 | E3H 1000 PR121/P-LSIG IN=1000A 3P F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Rated permanent current Iu
1000A
Adjustment range short-term delayed short-circuit release
1000 .. 10000A
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
Rated voltage
690 .. 690V
Integrated earth fault protection
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
DIN rail (top hat rail) mounting optional
Overload release current setting
400.0 .. 1000A
Complete device with protection unit
Position of connection for main current circuit
Back side
Motor drive integrated
Number of auxiliary contacts as change-over contact
4
Number of poles
3
Type of control element
Push button
Motor drive optional
Degree of protection (IP)
IP30
With switched-off indicator
Device construction
Built-in device fixed built-in technique
From same serie