

Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA059361R1 | E3H 1000 PR122/P-LSI IN=1000A 3P F HR

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1000A
Rated voltage
690 .. 690V
Integrated earth fault protection
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Overload release current setting
400.0 .. 1000A
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
600.0 .. 600.0A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Complete device with protection unit
Type of control element
Push button
Motor drive integrated
Number of poles
3
Number of auxiliary contacts as normally closed contact
0
Motor drive optional
Position of connection for main current circuit
Back side