Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Integrated earth fault protectionNo
Rated voltage690 - 690V
Number of auxiliary contacts as normally closed contact0
Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as normally open contact0
Adjustment range short-term delayed short-circuit release1000 - 10000A
Rated permanent current Iu1000A
Number of auxiliary contacts as change-over contact4
With switched-off indicatorYes
DIN rail (top hat rail) mounting optionalNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz75kA
Type of control elementPush button
Adjustment range undelayed short-circuit release1500.0 - 15000A
Motor drive integratedNo
Overload release current setting400.0 - 1000A
Degree of protection (IP)IP30
Complete device with protection unitYes
Motor drive optionalYes
Number of poles3
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device fixed built-in technique
Position of connection for main current circuitBack side
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA059389R1 | E3S 1000 PR121/P-LSI IN=1000A 3P F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Integrated earth fault protection

Rated voltage

690 .. 690V

Number of auxiliary contacts as normally closed contact

0

Type of electrical connection of main circuit

Bolt connection

Number of auxiliary contacts as normally open contact

0

Adjustment range short-term delayed short-circuit release

1000 .. 10000A

Rated permanent current Iu

1000A

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

DIN rail (top hat rail) mounting optional

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

75kA

Type of control element

Push button

Adjustment range undelayed short-circuit release

1500.0 .. 15000A

Motor drive integrated

Overload release current setting

400.0 .. 1000A

Degree of protection (IP)

IP30

Complete device with protection unit

Motor drive optional

Number of poles

3

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device fixed built-in technique

Position of connection for main current circuit

Back side

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.