Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA059402R1 | E3S 1000 PR122/P-LSI IN=1000A 3P W MP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Rated permanent current Iu
1000A
Rated voltage
690 .. 690V
Motor drive integrated
Degree of protection (IP)
IP30
Number of poles
3
Overload release current setting
400.0 .. 1000A
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
With switched-off indicator
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Type of control element
Push button
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
75kA
Adjustment range short-term delayed short-circuit release
600.0 .. 600.0A
Complete device with protection unit
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
With under voltage release
Motor drive optional