Aleta.hr
Main Product Image

1SDA070696R1 | E1.2N 250 EKIP TOUCH LSIG 3P F F

Code: 1613772

ManufacturerABB
Catalog number1SDA070696R1
EAN code8015644745462

















Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage releaseNo
Rated permanent current Iu250A
Adjustment range undelayed short-circuit release375.0 - 3750A
Integrated earth fault protectionYes
Adjustment range short-term delayed short-circuit release150.0 - 2500A
Position of connection for main current circuitBack side
Number of poles3
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally closed contact0
Degree of protection (IP)IP30
DIN rail (top hat rail) mounting optionalNo
Overload release current setting100.0 - 250A
Number of auxiliary contacts as normally open contact0
Rated voltage690 - 690V
Motor drive optionalYes
Complete device with protection unitYes
Type of control elementPush button
Motor drive integratedNo
With switched-off indicatorYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA
Type of electrical connection of main circuitBolt connection
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device fixed built-in technique
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA070696R1 | E1.2N 250 EKIP TOUCH LSIG 3P F F

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

250A

Adjustment range undelayed short-circuit release

375.0 .. 3750A

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

150.0 .. 2500A

Position of connection for main current circuit

Back side

Number of poles

3

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally closed contact

0

Degree of protection (IP)

IP30

DIN rail (top hat rail) mounting optional

Overload release current setting

100.0 .. 250A

Number of auxiliary contacts as normally open contact

0

Rated voltage

690 .. 690V

Motor drive optional

Complete device with protection unit

Type of control element

Push button

Motor drive integrated

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

66kA

Type of electrical connection of main circuit

Bolt connection

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device fixed built-in technique

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.