Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Adjustment range short-term delayed short-circuit release
378.0 - 6300A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Yes
Type of electrical connection of main circuit
Bolt connection
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Overload release current setting
252.0 - 630A
Rated permanent current Iu
630A
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
945.0 - 9450A
Type of control element
Push button
Number of poles
3
Complete device with protection unit
Yes
Motor drive optional
Yes
DIN rail (top hat rail) mounting optional
No
Motor drive integrated
No
With switched-off indicator
Yes
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
1SDA070729R1 | E1.2N 630 EKIP HI-TOUCH LSIG 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Adjustment range short-term delayed short-circuit release
378.0 .. 6300A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Overload release current setting
252.0 .. 630A
Rated permanent current Iu
630A
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
945.0 .. 9450A
Type of control element
Push button
Number of poles
3
Complete device with protection unit
Motor drive optional
DIN rail (top hat rail) mounting optional
Motor drive integrated
With switched-off indicator
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30