Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA070789R1 | E1.2B 1000 EKIP HI-TOUCH LSIG 3P F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
With integrated under voltage release
Number of auxiliary contacts as change-over contact
4
Overload release current setting
400.0 .. 1000A
Position of connection for main current circuit
Back side
Type of control element
Push button
Motor drive integrated
Rated voltage
690 .. 690V
With switched-off indicator
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Degree of protection (IP)
IP30
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
1000A
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Device construction
Built-in device fixed built-in technique
Complete device with protection unit
Number of poles
3