

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1000A
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
600.0 - 10000A
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Number of poles
3
Type of control element
Push button
Complete device with protection unit
Yes
Overload release current setting
400.0 - 1000A
With switched-off indicator
Yes
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
Motor drive integrated
No
Motor drive optional
Yes
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Bolt connection
Degree of protection (IP)
IP30
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Position of connection for main current circuit
Back side
Integrated earth fault protection
No
With under voltage release
No
Rated voltage
690 - 690V
From same serie
1SDA070792R1 | E1.2C 1000 EKIP DIP LSI 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1000A
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Number of poles
3
Type of control element
Push button
Complete device with protection unit
Overload release current setting
400.0 .. 1000A
With switched-off indicator
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Motor drive integrated
Motor drive optional
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Bolt connection
Degree of protection (IP)
IP30
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Position of connection for main current circuit
Back side
Integrated earth fault protection
With under voltage release
Rated voltage
690 .. 690V
From same serie
We use cookies to enhance your experience.