Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
400.0 - 1000A
Adjustment range short-term delayed short-circuit release
600.0 - 10000A
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Rated voltage
690 - 690V
Rated permanent current Iu
1000A
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of poles
3
Integrated earth fault protection
Yes
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Back side
Complete device with protection unit
Yes
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
No
Motor drive optional
Yes
With switched-off indicator
Yes
Degree of protection (IP)
IP30
From same serie
1SDA070807R1 | E1.2N 1000 EKIP G TOUCH LSIG 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
400.0 .. 1000A
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Rated voltage
690 .. 690V
Rated permanent current Iu
1000A
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of poles
3
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Back side
Complete device with protection unit
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
Motor drive optional
With switched-off indicator
Degree of protection (IP)
IP30
From same serie