Technical specifications

With integrated under voltage releaseNo
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Overload release current setting500.0 - 1250A
Rated permanent current Iu1250A
Number of auxiliary contacts as normally open contact0
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionYes
Adjustment range undelayed short-circuit release1875.0 - 18750A
Adjustment range short-term delayed short-circuit release750.0 - 12500A
Number of poles3
Type of control elementPush button
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact4
Complete device with protection unitYes
Motor drive optionalYes
Position of connection for main current circuitBack side
With switched-off indicatorYes
Degree of protection (IP)IP30
Motor drive integratedNo
Device constructionBuilt-in device fixed built-in technique
Type of electrical connection of main circuitBolt connection
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA070837R1 | E1.2C 1250 EKIP G TOUCH LSIG 3P F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated voltage

690 .. 690V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Overload release current setting

500.0 .. 1250A

Rated permanent current Iu

1250A

Number of auxiliary contacts as normally open contact

0

DIN rail (top hat rail) mounting optional

Suitable for DIN rail (top hat rail) mounting

Integrated earth fault protection

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

Adjustment range short-term delayed short-circuit release

750.0 .. 12500A

Number of poles

3

Type of control element

Push button

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

4

Complete device with protection unit

Motor drive optional

Position of connection for main current circuit

Back side

With switched-off indicator

Degree of protection (IP)

IP30

Motor drive integrated

Device construction

Built-in device fixed built-in technique

Type of electrical connection of main circuit

Bolt connection