Technical specifications
With integrated under voltage release
No
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Overload release current setting
640.0 - 1600A
Rated permanent current Iu
1600A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Rated voltage
690 - 690V
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Type of control element
Push button
Number of poles
3
Complete device with protection unit
Yes
Motor drive optional
Yes
Motor drive integrated
No
1SDA070867R1 | E1.2B 1600 EKIP G TOUCH LSIG 3P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Overload release current setting
640.0 .. 1600A
Rated permanent current Iu
1600A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Rated voltage
690 .. 690V
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Type of control element
Push button
Number of poles
3
Complete device with protection unit
Motor drive optional
Motor drive integrated