Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA070939R1 | E2.2S 1000 EKIP HI-TOUCH LSIG 3P FHR

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Overload release current setting
400.0 .. 1000A
Rated voltage
690 .. 690V
Number of auxiliary contacts as change-over contact
4
With integrated under voltage release
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Rated permanent current Iu
1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Integrated earth fault protection
Position of connection for main current circuit
Back side
Number of poles
3
Device construction
Built-in device fixed built-in technique
Type of control element
Push button
Motor drive integrated
Complete device with protection unit
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional