Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1250A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range short-term delayed short-circuit release
750.0 - 12500A
Overload release current setting
500.0 - 1250A
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
Number of poles
3
Type of control element
Push button
Motor drive integrated
No
Complete device with protection unit
Yes
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Yes
Position of connection for main current circuit
Back side
Device construction
Built-in device fixed built-in technique
With under voltage release
No
Degree of protection (IP)
IP30
From same serie
1SDA070966R1 | E2.2S 1250 EKIP TOUCH LSIG 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1250A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
Overload release current setting
500.0 .. 1250A
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
With switched-off indicator
Number of poles
3
Type of control element
Push button
Motor drive integrated
Complete device with protection unit
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Position of connection for main current circuit
Back side
Device construction
Built-in device fixed built-in technique
With under voltage release
Degree of protection (IP)
IP30