

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1250A
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
750.0 - 12500A
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Overload release current setting
500.0 - 1250A
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
With under voltage release
No
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Number of poles
3
Suitable for DIN rail (top hat rail) mounting
No
Type of control element
Push button
Complete device with protection unit
Yes
Device construction
Built-in device fixed built-in technique
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
From same serie
1SDA070970R1 | E2.2S 1250 EKIP G HI-TOUCH LSIG 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1250A
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Overload release current setting
500.0 .. 1250A
DIN rail (top hat rail) mounting optional
With switched-off indicator
With under voltage release
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Number of poles
3
Suitable for DIN rail (top hat rail) mounting
Type of control element
Push button
Complete device with protection unit
Device construction
Built-in device fixed built-in technique
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP30
From same serie
We use cookies to enhance your experience.