Technical specifications
With integrated under voltage release
No
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Rated permanent current Iu
1600A
Integrated earth fault protection
Yes
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Overload release current setting
640.0 - 1600A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Motor drive integrated
No
Motor drive optional
Yes
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
1SDA070989R1 | E2.2B 1600 EKIP HI-TOUCH LSIG 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Rated permanent current Iu
1600A
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Overload release current setting
640.0 .. 1600A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Motor drive integrated
Motor drive optional
Complete device with protection unit
Degree of protection (IP)
IP30