Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA070993R1 | E2.2N 1600 EKIP DIP LSIG 3P FHR

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of poles
3
Rated permanent current Iu
1600A
Number of auxiliary contacts as change-over contact
4
Overload release current setting
640.0 .. 1600A
With integrated under voltage release
Rated voltage
690 .. 690V
Degree of protection (IP)
IP30
Position of connection for main current circuit
Back side
Type of control element
Push button
Type of electrical connection of main circuit
Bolt connection
Complete device with protection unit
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
With switched-off indicator
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Motor drive integrated
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Device construction
Built-in device fixed built-in technique