Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA071003R1 | E2.2S 1600 EKIP DIP LSIG 3P FHR

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1600A
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Overload release current setting
640.0 .. 1600A
Degree of protection (IP)
IP30
Number of poles
3
With integrated under voltage release
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Type of control element
Push button
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Motor drive integrated
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Motor drive optional
Complete device with protection unit
With switched-off indicator
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection