- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1600A
Integrated earth fault protection
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Rated voltage
690 - 690V
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Overload release current setting
640.0 - 1600A
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
Yes
Number of poles
3
Type of control element
Push button
Complete device with protection unit
Yes
Motor drive optional
Yes
Position of connection for main current circuit
Back side
Motor drive integrated
No
Degree of protection (IP)
IP30
1SDA071005R1 | E2.2S 1600 EKIP TOUCH LSI 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1600A
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Rated voltage
690 .. 690V
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Overload release current setting
640.0 .. 1600A
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
Number of poles
3
Type of control element
Push button
Complete device with protection unit
Motor drive optional
Position of connection for main current circuit
Back side
Motor drive integrated
Degree of protection (IP)
IP30