Technical specifications

With integrated under voltage release

No

Rated permanent current Iu

2000A

Overload release current setting

800.0 - 2000A

Integrated earth fault protection

Yes

Rated voltage

690 - 690V

Adjustment range undelayed short-circuit release

3000.0 - 30000A

Adjustment range short-term delayed short-circuit release

1200.0 - 20000A

Device construction

Built-in device fixed built-in technique

Number of auxiliary contacts as change-over contact

4

Number of poles

3

With switched-off indicator

Yes

Type of electrical connection of main circuit

Bolt connection

Complete device with protection unit

Yes

Suitable for DIN rail (top hat rail) mounting

No

Number of auxiliary contacts as normally closed contact

0

Type of control element

Push button

DIN rail (top hat rail) mounting optional

No

Degree of protection (IP)

IP30

Motor drive integrated

No

Number of auxiliary contacts as normally open contact

0

Motor drive optional

Yes

Position of connection for main current circuit

Back side

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA071057R1 | E2.2H 2000 EKIP G TOUCH LSIG 3P FHR

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

2000A

Overload release current setting

800.0 .. 2000A

Integrated earth fault protection

Rated voltage

690 .. 690V

Adjustment range undelayed short-circuit release

3000.0 .. 30000A

Adjustment range short-term delayed short-circuit release

1200.0 .. 20000A

Device construction

Built-in device fixed built-in technique

Number of auxiliary contacts as change-over contact

4

Number of poles

3

With switched-off indicator

Type of electrical connection of main circuit

Bolt connection

Complete device with protection unit

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as normally closed contact

0

Type of control element

Push button

DIN rail (top hat rail) mounting optional

Degree of protection (IP)

IP30

Motor drive integrated

Number of auxiliary contacts as normally open contact

0

Motor drive optional

Position of connection for main current circuit

Back side

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA