Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
2500A
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
1000.0 - 2500A
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Number of poles
3
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
Degree of protection (IP)
IP30
Integrated earth fault protection
Yes
Motor drive optional
Yes
Complete device with protection unit
Yes
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Motor drive integrated
No
Position of connection for main current circuit
Back side
Type of control element
Push button
Type of electrical connection of main circuit
Bolt connection
From same serie
1SDA071063R1 | E2.2N 2500 EKIP DIP LSIG 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
2500A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
1000.0 .. 2500A
DIN rail (top hat rail) mounting optional
With switched-off indicator
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Number of poles
3
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Degree of protection (IP)
IP30
Integrated earth fault protection
Motor drive optional
Complete device with protection unit
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Motor drive integrated
Position of connection for main current circuit
Back side
Type of control element
Push button
Type of electrical connection of main circuit
Bolt connection