

Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA071071R1 | E2.2S 2500 EKIP DIP LI 3P FHR

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
2500A
With integrated under voltage release
Number of auxiliary contacts as normally closed contact
0
Number of poles
3
Overload release current setting
1000.0 .. 2500A
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Degree of protection (IP)
IP30
Rated voltage
690 .. 690V
Position of connection for main current circuit
Back side
Motor drive integrated
Number of auxiliary contacts as change-over contact
4
Adjustment range short-term delayed short-circuit release
- .. -A
Type of electrical connection of main circuit
Bolt connection
Type of control element
Push button
Motor drive optional
DIN rail (top hat rail) mounting optional
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Complete device with protection unit