Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Overload release current setting
1000.0 - 2500A
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Rated permanent current Iu
2500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Integrated earth fault protection
Yes
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Number of poles
3
Complete device with protection unit
Yes
Position of connection for main current circuit
Back side
Motor drive integrated
No
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Degree of protection (IP)
IP30
Motor drive optional
Yes
From same serie
1SDA071079R1 | E2.2S 2500 EKIP HI-TOUCH LSIG 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Overload release current setting
1000.0 .. 2500A
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Rated permanent current Iu
2500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Number of poles
3
Complete device with protection unit
Position of connection for main current circuit
Back side
Motor drive integrated
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Degree of protection (IP)
IP30
Motor drive optional
From same serie