Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
No
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Device construction
Built-in device fixed built-in technique
With under voltage release
No
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
Overload release current setting
1000.0 - 2500A
Position of connection for main current circuit
Back side
Motor drive integrated
No
Type of control element
Push button
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive optional
Yes
Rated permanent current Iu
2500A
Number of poles
3
From same serie
1SDA071088R1 | E2.2H 2500 EKIP HI-TOUCH LSI 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Device construction
Built-in device fixed built-in technique
With under voltage release
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Overload release current setting
1000.0 .. 2500A
Position of connection for main current circuit
Back side
Motor drive integrated
Type of control element
Push button
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive optional
Rated permanent current Iu
2500A
Number of poles
3
From same serie
We use cookies to enhance your experience.