Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
With integrated under voltage release
No
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
No
Suitable for DIN rail (top hat rail) mounting
No
Number of poles
3
With switched-off indicator
Yes
Position of connection for main current circuit
Back side
Type of electrical connection of main circuit
Bolt connection
Rated voltage
690 - 690V
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated permanent current Iu
2000A
Overload release current setting
800.0 - 2000A
Complete device with protection unit
Yes
Motor drive integrated
No
Type of control element
Push button
Motor drive optional
Yes
Degree of protection (IP)
IP30
From same serie
1SDA071101R1 | E4.2V 2000 EKIP DIP LI 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
With integrated under voltage release
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Number of poles
3
With switched-off indicator
Position of connection for main current circuit
Back side
Type of electrical connection of main circuit
Bolt connection
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated permanent current Iu
2000A
Overload release current setting
800.0 .. 2000A
Complete device with protection unit
Motor drive integrated
Type of control element
Push button
Motor drive optional
Degree of protection (IP)
IP30
From same serie