Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Rated permanent current Iu2500A
Overload release current setting1000.0 - 2500A
Adjustment range short-term delayed short-circuit release1500.0 - 25000A
Adjustment range undelayed short-circuit release3750.0 - 37500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
Device constructionBuilt-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
Number of poles3
Number of auxiliary contacts as change-over contact4
With under voltage releaseNo
Integrated earth fault protectionYes
With switched-off indicatorYes
Rated voltage690 - 690V
Type of electrical connection of main circuitBolt connection
Position of connection for main current circuitBack side
Type of control elementPush button
Complete device with protection unitYes
Degree of protection (IP)IP30
Motor drive optionalYes
Motor drive integratedNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA071126R1 | E4.2V 2500 EKIP TOUCH LSIG 3P FHR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

2500A

Overload release current setting

1000.0 .. 2500A

Adjustment range short-term delayed short-circuit release

1500.0 .. 25000A

Adjustment range undelayed short-circuit release

3750.0 .. 37500A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Device construction

Built-in device fixed built-in technique

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

Number of poles

3

Number of auxiliary contacts as change-over contact

4

With under voltage release

Integrated earth fault protection

With switched-off indicator

Rated voltage

690 .. 690V

Type of electrical connection of main circuit

Bolt connection

Position of connection for main current circuit

Back side

Type of control element

Push button

Complete device with protection unit

Degree of protection (IP)

IP30

Motor drive optional

Motor drive integrated

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.