Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Integrated earth fault protection
No
Device construction
Built-in device fixed built-in technique
Rated permanent current Iu
2500A
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Yes
Rated voltage
690 - 690V
With under voltage release
No
Type of control element
Push button
DIN rail (top hat rail) mounting optional
No
Motor drive optional
Yes
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Complete device with protection unit
Yes
Suitable for DIN rail (top hat rail) mounting
No
Number of poles
3
Motor drive integrated
No
Overload release current setting
1000.0 - 2500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Position of connection for main current circuit
Back side
From same serie
1SDA071128R1 | E4.2V 2500 EKIP HI-TOUCH LSI 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Rated permanent current Iu
2500A
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Rated voltage
690 .. 690V
With under voltage release
Type of control element
Push button
DIN rail (top hat rail) mounting optional
Motor drive optional
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Complete device with protection unit
Suitable for DIN rail (top hat rail) mounting
Number of poles
3
Motor drive integrated
Overload release current setting
1000.0 .. 2500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Position of connection for main current circuit
Back side
From same serie