Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA071159R1 | E4.2S 3200 EKIP HI-TOUCH LSIG 3P FHR

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 .. 690V
With integrated under voltage release
Overload release current setting
1280.0 .. 3200A
Degree of protection (IP)
IP30
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Motor drive optional
With switched-off indicator
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Suitable for DIN rail (top hat rail) mounting
Motor drive integrated
Device construction
Built-in device fixed built-in technique
Rated permanent current Iu
3200A
Integrated earth fault protection
Number of poles
3
Position of connection for main current circuit
Back side
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Type of control element
Push button
Complete device with protection unit