Aleta.hr
Main Product Image

1SDA071168R1 | E4.2H 3200 EKIP HI-TOUCH LSI 3P FHR

Code: 1614174

ManufacturerRAZNO
Catalog number1SDA071168R1
Type
EAN code8015644750183

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Type of electrical connection of main circuit

Bolt connection

Adjustment range short-term delayed short-circuit release

1920.0 - 32000A

Integrated earth fault protection

No

Rated permanent current Iu

3200A

Adjustment range undelayed short-circuit release

4800.0 - 48000A

Overload release current setting

1280.0 - 3200A

Rated voltage

690 - 690V

Suitable for DIN rail (top hat rail) mounting

No

With under voltage release

No

Device construction

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

No

Position of connection for main current circuit

Back side

Motor drive integrated

No

With switched-off indicator

Yes

Number of poles

3

Type of control element

Push button

Complete device with protection unit

Yes

Number of auxiliary contacts as change-over contact

4

Degree of protection (IP)

IP30

Motor drive optional

Yes


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA071168R1 | E4.2H 3200 EKIP HI-TOUCH LSI 3P FHR

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Type of electrical connection of main circuit

Bolt connection

Adjustment range short-term delayed short-circuit release

1920.0 .. 32000A

Integrated earth fault protection

Rated permanent current Iu

3200A

Adjustment range undelayed short-circuit release

4800.0 .. 48000A

Overload release current setting

1280.0 .. 3200A

Rated voltage

690 .. 690V

Suitable for DIN rail (top hat rail) mounting

With under voltage release

Device construction

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

Position of connection for main current circuit

Back side

Motor drive integrated

With switched-off indicator

Number of poles

3

Type of control element

Push button

Complete device with protection unit

Number of auxiliary contacts as change-over contact

4

Degree of protection (IP)

IP30

Motor drive optional