

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
Yes
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
1920.0 - 32000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 - 690V
Overload release current setting
1280.0 - 3200A
Type of electrical connection of main circuit
Bolt connection
Rated permanent current Iu
3200A
Adjustment range undelayed short-circuit release
4800.0 - 48000A
With switched-off indicator
Yes
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
4
With under voltage release
No
Motor drive integrated
No
Degree of protection (IP)
IP30
Number of poles
3
Position of connection for main current circuit
Back side
Type of control element
Push button
Complete device with protection unit
Yes
Motor drive optional
Yes
1SDA071180R1 | E4.2V 3200 EKIP G HI-TOUCH LSIG 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 .. 690V
Overload release current setting
1280.0 .. 3200A
Type of electrical connection of main circuit
Bolt connection
Rated permanent current Iu
3200A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
4
With under voltage release
Motor drive integrated
Degree of protection (IP)
IP30
Number of poles
3
Position of connection for main current circuit
Back side
Type of control element
Push button
Complete device with protection unit
Motor drive optional
We use cookies to enhance your experience.