Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Overload release current setting
1600.0 - 4000A
Integrated earth fault protection
Yes
Rated permanent current Iu
4000A
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Number of poles
3
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Motor drive optional
Yes
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
No
Suitable for DIN rail (top hat rail) mounting
No
1SDA071207R1 | E4.2S 4000 EKIP G TOUCH LSIG 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Overload release current setting
1600.0 .. 4000A
Integrated earth fault protection
Rated permanent current Iu
4000A
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Number of poles
3
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Motor drive optional
Complete device with protection unit
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
Suitable for DIN rail (top hat rail) mounting
We use cookies to enhance your experience.