Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Overload release current setting
1600.0 - 4000A
Rated permanent current Iu
4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Integrated earth fault protection
Yes
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
Type of control element
Push button
Number of poles
3
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
1SDA071209R1 | E4.2S 4000 EKIP HI-TOUCH LSIG 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Overload release current setting
1600.0 .. 4000A
Rated permanent current Iu
4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Integrated earth fault protection
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
DIN rail (top hat rail) mounting optional
With switched-off indicator
Type of control element
Push button
Number of poles
3
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP30
Complete device with protection unit