

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 - 690V
Rated permanent current Iu
4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Overload release current setting
1600.0 - 4000A
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Integrated earth fault protection
No
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Number of poles
3
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Motor drive optional
Yes
Complete device with protection unit
Yes
Motor drive integrated
No
Suitable for DIN rail (top hat rail) mounting
No
Degree of protection (IP)
IP30
With under voltage release
No
From same serie
1SDA071212R1 | E4.2H 4000 EKIP DIP LSI 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 .. 690V
Rated permanent current Iu
4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Overload release current setting
1600.0 .. 4000A
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Number of poles
3
DIN rail (top hat rail) mounting optional
With switched-off indicator
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Motor drive optional
Complete device with protection unit
Motor drive integrated
Suitable for DIN rail (top hat rail) mounting
Degree of protection (IP)
IP30
With under voltage release
From same serie
We use cookies to enhance your experience.