Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

4000A

Rated voltage

690 - 690V

Adjustment range short-term delayed short-circuit release

2400.0 - 40000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Overload release current setting

1600.0 - 4000A

Integrated earth fault protection

Yes

Type of electrical connection of main circuit

Bolt connection

Device construction

Built-in device fixed built-in technique

Adjustment range undelayed short-circuit release

6000.0 - 60000A

DIN rail (top hat rail) mounting optional

No

Suitable for DIN rail (top hat rail) mounting

No

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

Yes

Number of poles

3

With under voltage release

No

Complete device with protection unit

Yes

Position of connection for main current circuit

Back side

Type of control element

Push button

Motor drive integrated

No

Motor drive optional

Yes

Degree of protection (IP)

IP30

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA071220R1 | E4.2H 4000 EKIP G HI-TOUCH LSIG 3P FHR

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

4000A

Rated voltage

690 .. 690V

Adjustment range short-term delayed short-circuit release

2400.0 .. 40000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Overload release current setting

1600.0 .. 4000A

Integrated earth fault protection

Type of electrical connection of main circuit

Bolt connection

Device construction

Built-in device fixed built-in technique

Adjustment range undelayed short-circuit release

6000.0 .. 60000A

DIN rail (top hat rail) mounting optional

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as change-over contact

4

With switched-off indicator

Number of poles

3

With under voltage release

Complete device with protection unit

Position of connection for main current circuit

Back side

Type of control element

Push button

Motor drive integrated

Motor drive optional

Degree of protection (IP)

IP30