

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Overload release current setting
1600.0 - 4000A
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Integrated earth fault protection
Yes
Rated voltage
690 - 690V
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Bolt connection
Rated permanent current Iu
4000A
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Number of auxiliary contacts as change-over contact
4
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Type of control element
Push button
Position of connection for main current circuit
Back side
Number of poles
3
Motor drive optional
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
1SDA071239R1 | E6.2H 4000 EKIP HI-TOUCH LSIG 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Overload release current setting
1600.0 .. 4000A
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Integrated earth fault protection
Rated voltage
690 .. 690V
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Bolt connection
Rated permanent current Iu
4000A
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Number of auxiliary contacts as change-over contact
4
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Type of control element
Push button
Position of connection for main current circuit
Back side
Number of poles
3
Motor drive optional
Motor drive integrated
Degree of protection (IP)
IP30
Complete device with protection unit
We use cookies to enhance your experience.