Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Rated permanent current Iu
4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
1600.0 - 4000A
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Adjustment range undelayed short-circuit release
6000.0 - 60000A
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
Number of poles
3
Motor drive optional
Yes
With switched-off indicator
Yes
Type of control element
Push button
Motor drive integrated
No
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
1SDA071249R1 | E6.2V 4000 EKIP HI-TOUCH LSIG 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Rated permanent current Iu
4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
1600.0 .. 4000A
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Number of poles
3
Motor drive optional
With switched-off indicator
Type of control element
Push button
Motor drive integrated
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
We use cookies to enhance your experience.