Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Integrated earth fault protection
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
690 - 690V
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
945.0 - 9450A
Overload release current setting
252.0 - 630A
DIN rail (top hat rail) mounting optional
No
Rated permanent current Iu
630A
Adjustment range short-term delayed short-circuit release
378.0 - 6300A
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device fixed built-in technique
Number of poles
4
With switched-off indicator
Yes
Degree of protection (IP)
IP30
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
Type of control element
Push button
Type of electrical connection of main circuit
Bolt connection
1SDA071333R1 | E1.2B 630 EKIP DIP LSIG 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Suitable for DIN rail (top hat rail) mounting
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
945.0 .. 9450A
Overload release current setting
252.0 .. 630A
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
630A
Adjustment range short-term delayed short-circuit release
378.0 .. 6300A
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device fixed built-in technique
Number of poles
4
With switched-off indicator
Degree of protection (IP)
IP30
Position of connection for main current circuit
Back side
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Motor drive integrated
Motor drive optional
Type of control element
Push button
Type of electrical connection of main circuit
Bolt connection