Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
630A
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
378.0 - 6300A
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
No
Device construction
Built-in device fixed built-in technique
With switched-off indicator
Yes
DIN rail (top hat rail) mounting optional
No
Number of poles
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
252.0 - 630A
With under voltage release
No
Adjustment range undelayed short-circuit release
945.0 - 9450A
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Motor drive optional
Yes
Type of control element
Push button
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
Type of electrical connection of main circuit
Bolt connection
1SDA071358R1 | E1.2N 630 EKIP HI-TOUCH LSI 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
630A
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
378.0 .. 6300A
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
With switched-off indicator
DIN rail (top hat rail) mounting optional
Number of poles
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
252.0 .. 630A
With under voltage release
Adjustment range undelayed short-circuit release
945.0 .. 9450A
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Motor drive optional
Type of control element
Push button
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive integrated
Type of electrical connection of main circuit
Bolt connection
We use cookies to enhance your experience.