Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
800A
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Overload release current setting
320.0 - 800A
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
Yes
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
Position of connection for main current circuit
Back side
Type of control element
Push button
Motor drive integrated
No
Complete device with protection unit
Yes
Motor drive optional
Yes
Degree of protection (IP)
IP30
1SDA071373R1 | E1.2B 800 EKIP DIP LSIG 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
800A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Overload release current setting
320.0 .. 800A
Type of electrical connection of main circuit
Bolt connection
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
Position of connection for main current circuit
Back side
Type of control element
Push button
Motor drive integrated
Complete device with protection unit
Motor drive optional
Degree of protection (IP)
IP30