Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Adjustment range short-term delayed short-circuit release
600.0 - 10000A
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
400.0 - 1000A
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Rated permanent current Iu
1000A
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Motor drive integrated
No
Number of auxiliary contacts as change-over contact
4
Number of poles
4
With switched-off indicator
Yes
Complete device with protection unit
Yes
Motor drive optional
Yes
With under voltage release
No
Position of connection for main current circuit
Back side
Type of control element
Push button
Degree of protection (IP)
IP30
1SDA071420R1 | E1.2B 1000 EKIP G HI-TOUCH LSIG 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
400.0 .. 1000A
Device construction
Built-in device fixed built-in technique
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Rated permanent current Iu
1000A
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Motor drive integrated
Number of auxiliary contacts as change-over contact
4
Number of poles
4
With switched-off indicator
Complete device with protection unit
Motor drive optional
With under voltage release
Position of connection for main current circuit
Back side
Type of control element
Push button
Degree of protection (IP)
IP30