Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1250A
Integrated earth fault protection
No
Suitable for DIN rail (top hat rail) mounting
No
With under voltage release
No
Number of auxiliary contacts as change-over contact
4
Rated voltage
690 - 690V
Degree of protection (IP)
IP30
Motor drive integrated
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Adjustment range short-term delayed short-circuit release
750.0 - 12500A
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Yes
Number of poles
4
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Complete device with protection unit
Yes
DIN rail (top hat rail) mounting optional
No
Type of control element
Push button
Motor drive optional
Yes
Position of connection for main current circuit
Back side
Overload release current setting
500.0 - 1250A
From same serie
1SDA071468R1 | E1.2C 1250 EKIP HI-TOUCH LSI 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1250A
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
With under voltage release
Number of auxiliary contacts as change-over contact
4
Rated voltage
690 .. 690V
Degree of protection (IP)
IP30
Motor drive integrated
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Number of poles
4
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Complete device with protection unit
DIN rail (top hat rail) mounting optional
Type of control element
Push button
Motor drive optional
Position of connection for main current circuit
Back side
Overload release current setting
500.0 .. 1250A
From same serie