

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
With integrated under voltage release
No
Rated voltage
690 - 690V
Integrated earth fault protection
No
Rated permanent current Iu
1250A
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
500.0 - 1250A
Motor drive optional
Yes
Device construction
Built-in device fixed built-in technique
Degree of protection (IP)
IP30
With switched-off indicator
Yes
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Complete device with protection unit
Yes
Number of poles
4
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Back side
DIN rail (top hat rail) mounting optional
No
Motor drive integrated
No
From same serie
1SDA071471R1 | E1.2N 1250 EKIP DIP LI 4P F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
With integrated under voltage release
Rated voltage
690 .. 690V
Integrated earth fault protection
Rated permanent current Iu
1250A
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
500.0 .. 1250A
Motor drive optional
Device construction
Built-in device fixed built-in technique
Degree of protection (IP)
IP30
With switched-off indicator
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Complete device with protection unit
Number of poles
4
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Back side
DIN rail (top hat rail) mounting optional
Motor drive integrated
From same serie
We use cookies to enhance your experience.