Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA071502R1 | E1.2C 1600 EKIP DIP LSI 4P F F

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Motor drive integrated
Type of electrical connection of main circuit
Bolt connection
Degree of protection (IP)
IP30
Overload release current setting
640.0 .. 1600A
Rated voltage
690 .. 690V
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
With under voltage release
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
DIN rail (top hat rail) mounting optional
Number of poles
4
Integrated earth fault protection
Type of control element
Push button
Position of connection for main current circuit
Front side
Rated permanent current Iu
1600A
Complete device with protection unit
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Device construction
Built-in device fixed built-in technique