

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
600.0 - 10000A
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
400.0 - 1000A
Device construction
Built-in device fixed built-in technique
Rated voltage
690 - 690V
Integrated earth fault protection
Yes
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Back side
Number of poles
4
Motor drive integrated
No
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Type of control element
Push button
Motor drive optional
Yes
1SDA071573R1 | E2.2H 1000 EKIP DIP LSIG 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
400.0 .. 1000A
Device construction
Built-in device fixed built-in technique
Rated voltage
690 .. 690V
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Back side
Number of poles
4
Motor drive integrated
Degree of protection (IP)
IP30
Complete device with protection unit
Type of control element
Push button
Motor drive optional
We use cookies to enhance your experience.