Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Overload release current setting
500.0 - 1250A
Rated permanent current Iu
1250A
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Complete device with protection unit
Yes
DIN rail (top hat rail) mounting optional
No
Motor drive optional
Yes
Adjustment range short-term delayed short-circuit release
750.0 - 12500A
Type of control element
Push button
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Number of poles
4
Rated voltage
690 - 690V
Motor drive integrated
No
Degree of protection (IP)
IP30
From same serie
1SDA071599R1 | E2.2S 1250 EKIP HI-TOUCH LSIG 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Overload release current setting
500.0 .. 1250A
Rated permanent current Iu
1250A
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Complete device with protection unit
DIN rail (top hat rail) mounting optional
Motor drive optional
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
Type of control element
Push button
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Back side
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Number of poles
4
Rated voltage
690 .. 690V
Motor drive integrated
Degree of protection (IP)
IP30
From same serie