1SDA071607R1 | E2.2H 1250 EKIP G TOUCH LSIG 4P FHR
Code: 1614533

1SDA071607R1 | E2.2H 1250 EKIP G TOUCH LSIG 4P FHR

With integrated under voltage release
Rated permanent current Iu
1250A
Overload release current setting
500.0 .. 1250A
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Device construction
Built-in device fixed built-in technique
Rated voltage
690 .. 690V
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Back side
Number of poles
4
Motor drive optional
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Motor drive integrated
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Degree of protection (IP)
IP30