Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Overload release current setting
640.0 - 1600A
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Integrated earth fault protection
No
Position of connection for main current circuit
Back side
Complete device with protection unit
Yes
Motor drive integrated
No
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Type of control element
Push button
With switched-off indicator
Yes
Motor drive optional
Yes
Number of poles
4
Type of electrical connection of main circuit
Bolt connection
1SDA071625R1 | E2.2N 1600 EKIP TOUCH LSI 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Overload release current setting
640.0 .. 1600A
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Integrated earth fault protection
Position of connection for main current circuit
Back side
Complete device with protection unit
Motor drive integrated
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Type of control element
Push button
With switched-off indicator
Motor drive optional
Number of poles
4
Type of electrical connection of main circuit
Bolt connection