Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA071642R1 | E2.2H 1600 EKIP DIP LSI 4P FHR

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
640.0 .. 1600A
Rated permanent current Iu
1600A
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Back side
With switched-off indicator
Rated voltage
690 .. 690V
Type of control element
Push button
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
Degree of protection (IP)
IP30
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Device construction
Built-in device fixed built-in technique
Integrated earth fault protection
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
With under voltage release
Complete device with protection unit